IS 875 (Part 3): 2015 Structural Design Example
Detailed Verification & Calculation Analysis for Cladding & Structural Elements
1. Structural Parameters & Inputs
The calculation considers a standard 4-story commercial structure situated in New Delhi. Parameters used within the automated script execution model are detailed below:
| Parameter Description | Code Symbol | Selected Value | Reference / Remarks |
|---|---|---|---|
| Basic Wind Speed | Vb | 44.0 m/s | New Delhi (Appendix A, Table 1) |
| Risk Coefficient (Design Life) | k1 | 1.00 | Class B structure (50-year design life) |
| Terrain Category & Structure Size | — | Cat 3, Size B | Suburban area; medium building dimension |
| Terrain & Height Factor | k2 | 1.1030 | Interpolated at z = 12.0m (Table 2) |
| Topography Factor | k3 | 1.00 | Flat ground (Slope ≤ 3°) |
| Importance Factor (Cyclonic) | k4 | 1.00 | Non-cyclonic industrial zone |
| External Pressure Coeff. | Cpe | -1.30 | Typical overall cladding/façade suction |
| Internal Pressure Coeff. | Cpi | -0.20 | Normal building envelope (Closed) |
| Tributary / Panel Area | A | 2.00 m² | Design window glass frame element |
2. Step-by-Step Mathematical Derivation
Step 2.1: Design Wind Speed (Vz)
The design wind speed at height z is calculated by modifying basic wind speed with environmental factors:
Vz = 44.0 × 1.00 × 1.1030 × 1.00 × 1.00 = 48.532 m/s
Step 2.2: Design Wind Pressure (pz)
The basic design velocity pressure at height z is determined from kinetic energy equations defined in Clause 7.2:
pz = 0.6 × (48.532)² = 0.6 × 2355.355 = 1413.213 N/m² (1.413 kN/m²)
Step 2.3: Net Pressure Combinations (pnet)
Net surface pressure action depends on internal and external differential air pressure profiles:
pnet,A = pz × (Cpe + Cpi) = 1413.213 × (-1.30 + (-0.20)) = -2119.820 N/m²
Case B (Opposing Internal Action):
pnet,B = pz × (Cpe - Cpi) = 1413.213 × (-1.30 - (-0.20)) = -1554.534 N/m²
Step 2.4: Total Design Force on Panel (F)
Total localized suction force applied across the 2.0 m² tributary element surface:
FB = pnet,B × A = -1554.534 N/m² × 2.0 m² = -3109.068 N (-3.11 kN)
3. Calculation Summary & Verification Output
wc_example(). The negative signs indicate outward suction pressure on the building face, which governs the structural design of exterior wall brackets, mullion anchors, and glazing structural silicon seams as per IS 875 (Part 3): 2015 limits.